HP SureStore E Disk Array XP512/XP48 Owner's Guide
44
HP SureStore E Disk Array XP512/XP48: Owner’s Guide
.
Table 8. 3-Phase 60 Hz Operation
Specification 60 Hz-V1 60 Hz-V2s 60 Hz-V3
Nominal rated voltage (vac) 200 208 230
Minimum operating voltage (vac) 184 191 212
Maximum operating voltage (vac) 212 220 244
Rated line current (arms) 15 14.7 13.2
Dropout carry-through time at
minimum line voltage (ms)
500 500 500
Table 9. 3-Phase 50 Hz Operation
50 Hz-V1 50 Hz-V2s 50 Hz-V3 50 Hz-V4 50 Hz-V5 50 Hz-V6 50 Hz-V7
Nominal rated voltage (vac) 200 220 230 240 380 400 415
Minimum operating voltage
(vac)
184 202 212 221 350 368 382
Maximum operating voltage
(vac)
212 233 244 254 403 424 440
Rated line current (arms) 15 13.8 13.2 12.6 9.9 9.6 9.5
Dropout carry-through time
at minimum line voltage
(ms)
500 500 500 500 500 500 500