HP SureStore E Disk Array XP512 Site Prep Guide
64
HP SureStore E Disk Array XP512: Site Prep Guide
Heat Dissipation
The following table describes the heat dissipation of the DKC and DKU
(fully loaded):
Heat Dissipation DKU
1
1. DKU fully configured with 18GB HDDs
DKC
2
2. DKU fully configured with 47GB or 72GB HDDs
DKC
3
3. DKC configured with 8GB Cache Memory, two fibre 8-port adapters
and one additional disk adapter
DKC
4
4. DKC fully configured
Power consumption (kVA) 3.14 3.72 1.57 2.41
Heat dissipation (kW) 2.85 3.43 1.46 2.32
BTUs per hour 9,727 11,707 4,983 7,918
kcal per hour 2,451 2,949 1,255 1,995