HP SureStore E Disk Array XP512 Site Prep Guide

Preparing for Installation
43
1-Phase 50Hz Operation 50Hz-V1 50Hz-V2s 50Hz-V3 50Hz-V4
Nominal rated voltage (Vac) 200 220 230 240
Minimum Operating Voltage
(Vac)
184 202 212 221
Maximum Operating Voltage
(Vac)
212 233 244 254
Rated Line Current: DKU
(Arms)
12.3 11.1 10.8 10.5
Rated Line Current: DKC
(Arms)
5.7 5.3 5.2 5.1
Dropout carry-thru time at
minimum line voltage (ms)
500 500 500 500
3-Phase 60Hz Operation 60Hz-V1 60Hz-V2s 60Hz-V3
Nominal rated voltage (Vac) 200 208 230
Minimum operating voltage
(Vac)
184 191 212
Maximum operating voltage
(Vac)
212 220 244
Rated line current (Arms) 15 14.7 13.2
Dropout carry-thru time at
minimum line voltage (ms)
500 500 500
Nominal rated voltage (Vac) 200 208 230