HP SureStore E Disk Array XP512: Site Prep Guide
Frequency
AC line frequency is normally determined by your local power providers.
In some cases, electrical power is supplied by motor-generators. Shifts in
AC line frequency can cause system errors. Your HP CE can monitor the
frequency of the input AC line power and make recommendations, if
necessary.
AC Line Voltage Requirements for the HP SureStore E Disk Array XP512
The basic AC power requirements are as follows:
1-Phase 60Hz Operation 60Hz-V1 60Hz-V2s 60Hz-V3
Nominal rated voltage (Vac) 200 208 230
Minimum operating voltage
(Vac)
184 191 212
Maximum operating voltage
(Vac)
212 220 244
Rated line current: DKU
(Arms)
12.3 11.9 10.8
Rated line current: DKC
(Arms)
5.7 5.6 5.2
Dropout carry-thru time at
minimum line voltage (ms)
500 500 500