HP SureStore E Disk Array XP512 Site Prep Guide

Preparing for Installation
37
Adding Additional DKUs
Your disk array can consist of up to 6 DKUs. A minimum configuration
consists of one DKC and one DKU. The following diagram depicts the
order and placement of additional DKUs:
Required Clearance (a + b) (m)
Floor Load Rating
(kg/m
2
)
Clearance (C) (m)
C=0 C=0.2 C=0.4 C=0.6 C=1.0
500 0.20000
450 0.9 0.3 0 0 0
400 1.8 1.1 0.6 0.2 0
350 3.2 2.4 1.7 1.1 0.3
300 5.4 4.3 3.4 2.7 1.6
DKU 4
DKU 3
DKC
DKU 2
DKU 6
DKU 5
DKU 1