HP StorageWorks XP12000 Disk Array Site Preparation Guide (AE002-96040, March 2008)

240 VAC230 VAC220 VAC208 VAC200 VACParameter
3030303030Recommended circuit breakers (amps)
44444Number of circuit breakers
6060606060
Dropout carry-through time at
minimum line voltage (ms)
Table 28 30-amp, 50 or 60 Hz, three-phase DKU power specifications
415
VAC
400
VAC
380
VAC
240
VAC
230
VAC
220
VAC
208
VAC
200
VAC
Parameter
382368350221212202191184
Minimum operating voltage
(VAC)
440424403254244233220212
Maximum operating voltage
(VAC)
5.05.25.58.79.09.410.010.4
Rated line current per power
cord (amps RMS)
22222222Number of power cords
3030303030303030
Recommended circuit breakers
(amps)
22222222Number of circuit breakers
6060606060606060
Dropout carry-through time at
minimum line voltage (ms)
Receptacle part numbers and ordering information
Table 29 lists the plug and receptacle part numbers for 60 Hz configurations of the HP XP12000 disk
array.
Table 29 Plug and receptacle part numbers
ReceptaclePlugBreaker ratingPower source
Russellstoll 3933 (alt. 9C33U0) or 3753
(alt. 9R33U0W)
Russellstoll 3750DP30 A
Single-phase
Russellstoll 9C53U2 or 9R53U2WRussellstoll 9P53U250 A
Russellstoll 3934 (alt. 9C34U0) or 3754
(alt. 9R34U0W)
Russellstoll 3760PDG30 AThree-phase
Russellstoll connectors are available through most electrical distributors. HP has arranged for the
distributors listed below to stock these connectors. These distributors can ship worldwide via your
preferred carrier.
Beck Electrical Supply, 2775 Goodrick Avenue, Richmond, CA 94801, USA Telephone: (800)
466-4395, Fax: (800) 466-5442. Contact: Ken Mogan, casales@beckelectric.com.
XP12000 Disk Array Site Preparation Guide 51