You should not see any condensation in or around the disk array under any conditions. There is no
procedure for recovery from moisture condensation.
Table 12 Humidity specifications
Noncondensing relative humidity (RH)Humidity range type
50% to 55%
Recommended operating humidity range at 22 degrees C (71
degrees F)
20% to 80%Operating humidity range at 22 degrees C (71 degrees F)
8% to 90%Nonoperating humidity range
5% to 95%
Shipping and storage humidity range (product packed in factory
packing)
26 degrees C79 degrees FOperating maximum wet bulb temperature
27 degrees C81 degrees FNonoperating maximum wet bulb temperature
29 degrees C84 degrees FShipping and storage maximum wet bulb temperature
Mechanical vibration specifications
Continuous vibration can cause a slow degradation of mechanical parts and, when severe, can cause
data errors in disk drives. Mechanical connections such as printed circuit assembly (PCA) conductors,
cable connectors, and processor backplane wiring can also be affected by vibrations. Vibration
specifications apply to all three axes. For specification tests, see ASTM D999-91 Standard Methods
for Vibration Testing of Shipping Containers.
Table 13 Mechanical vibration specifications
SpecificationCondition
0.25 mm, 5–10 Hz 0.05 G, 10–300 HzOperating
2.5 mm, 5–10 Hz 0.5 G, 10–70 Hz 0.05 mm, 70–99 Hz 1.0
G, 99–300 Hz
Nonoperating
0.5 G, 15 min. (at four most severe resonances between 5 and
200 Hz)
Shipping and storage (product packed in
the factory)
Shock specifications
Table 14 lists shock specifications. For horizontal shock testing methods, see ASTM D5277-92 Standard
Test Methods for Performing Programmed Horizontal Impacts Using an Inclined Impact Tester. For
vertical shock testing methods, see ASTM D6055-96 Standard Test Methods for Mechanical Handling
of Unitized Loads and Large Shipping Cases and Crates.
Table 14 Shock specifications
SpecificationCondition
NoneOperating
8 G, 15 msNonoperating