HP StorageWorks XP10000 Disk Array Site Preparation Guide (AE102-96014, March 2008)

Figure 4 Primary rack clearance requirements
The letters a, b, and c in Figure 4 refer to the following:
Clearance a is the space between the service clearance at the left side of the array (100 mm
minimum for installing the kick plate) and any other object, such as a desk or wall.
Clearance b is the space between the service clearance at the right side of the array (100 mm
for the kick plate) and any other object.
Clearance c is the space between the service clearance at the front of the array and any other
object.
Use the value of c and your floor load rating in the following procedure to determine your required
clearances:
1. Determine how much space you can assign to clearance c. For maintenance purposes, try to
make c larger (1000 mm) rather than smaller (0 cm). The smaller c is, the larger a and b must
be.
XP10000 Disk Array Site Preparation Guide 29