HP StorageWorks XP10000 Disk Array Site Preparation Guide (AE102-96014, March 2008)

Total weightQuantityWeightDescriptionPart Number
Total weight of your configuration
Weight calculation example
Total
weight
QuantityWeightDescriptionPart Number
740.01 =740 x
HP XP10000 19" Primary Rack, disk
controller, base disk chassis for up to 60
HDDs, power supplies, base batteries for up
to 12 GB cache and up to 3 GB Shared
Memory
AE102A
12.81 =12.8 x
HP XP12000/10000 32-Port 2-Gbps FC
CHIP
AE007A
0.41 =0.44 xHP XP12000/10000 4-GB Cache MemoryAE025A
0.43 =0.13 xHP XP12000/10000 1-GB Shared MemoryAE030A
177.01 =177.0 x
HP XP10000 Disk Chassis (holds up to 60
drives)
AE104B
11.01 =11.0 xHP XP10000 16-Port FC SW CHIP 8-Port ACPAE105B
17.61 =17.6 xHP XP10000 BatteryAE110B
246.428 =8.8 xHP XP10000 300-GB 10k-rpm Array GroupAE123B
17.68 =2.2 xHP XP10000 300-GB 10k-rpm Spare DiskAE123BS
1223.2Total unpackaged weight of your configuration (rounded)
Delivery space requirements
The delivery area must provide enough space and floor strength to support the packaged equipment
cartons for the disk array. For packaged dimensions and weights, see
Dimensions and weights” on page 19.
CAUTION:
Make sure that your doorways and hallways provide enough clearance to move the equipment safely from
the delivery area to the computer room. Permanent obstructions such as pillars or narrow doorways can
cause equipment damage. If necessary, plan for the removal of walls or doors.
Site requirements for the XP10000 disk array22