HP StorageWorks XP10000 Disk Array Site Preparation Guide (AE102-96014, March 2008)
You can add more disk chassis in the order shown in Figure 1: R0 (#3), R1 (#4), R2 (#7), and R3
(#8). Your HP support representative can add disk chassis and disk drives online without interruptions
to applications or hosts. Additional details about each rack follow.
Primary rack expansion
In addition to the basic disk chassis (R0), you can expand the disk array in the primary rack as follows:
• Add one 60-disk chassis (R1) to the top space of the primary rack (#4). This provides a total of
120 drives.
Secondary rack
You can add a second 19-inch rack (#6) with additional disk units as follows:
• Add one 60-disk chassis to the second rack for a total of 180 drives (#7)
• Add a second 60-disk chassis to the secondary rack for a total of 240 drives (#8)
Dimensions and weights
Use the packaged values when determining delivery space and loading requirements and unpackaged
values during space and floor load planning. In the USA, most shipments use a special carrier process
in which frames are shipped without pallets, ramps, or cartons. In these cases, the packaged weight
is the unpackaged weight plus 23 kg (50 lb).
Table 2 Rack dimensions and weights
Packaged rackUnpackaged rackRack specification
950 mm, 37.4 inches610 mm, 24.0 inchesWidth
1110 mm, 43.7 inches925 mm, 36.4 inchesDepth
2030 mm, 79.9 inches1920 mm, 75.6 inchesHeight
448.5 kg, 989 lbs335.5 kg, 740 lbsWeight, primary rack, basic
690 kg, 1521 lbs577 kg, 1272 lbsWeight, primary rack, maximum
586 kg, 1292 lbs473 kg, 1043 lbsWeight second rack, maximum
Component weights
The following table provides approximate weights of additional disk array components. The number
of disk drives is the main factor accounting for total weight of the disk array. Actual weight of the
array racks is the minimum rack weight plus the weight of all additional components.
Table 3 Component weights
lbkgDescriptionProduct
11.05.0HP XP12000/10000 16-port 2-Gbps FC CHIPAE006A
12.85.8HP XP12000/10000 32-Port 2-Gbps FC CHIPAE007A
0.040.02HP XP12000/10000 2-Gbps FC SFP LW TransceiverAE008A
XP10000 Disk Array Site Preparation Guide 19