HP StorageWorks XP10000 Disk Array Owner's Guide (AE102-96013, March 2008)

PS-ON turns green.
MESSAGE LED may turn amber if the system is not configured for remote support, signifying a SIM
was generated because the system lost power unexpectedly.
READY LED turns green, signifying the system is ready.
CAUTION:
Powering on the disk array can take several minutes. Power on is complete only when the READY LED
turns green.
Operating specifications
This section provides some general specifications. For complete specifications, see the system site
preparation guide, available on the HP XP Disk Array website:
http://h18006.www1.hp.com/storage/xparrays.html
Temperature
Table 4 Temperature specifications
RangeTemperature range type
21 to 24 degrees C70 to 75 degrees FRecommended operating temperature range
16 to 32 degrees C61 to 89 degrees FOperating temperature
–10 to +43 degrees C14 to 109 degrees FNon-operating temperature range
–25 to +60 degrees C–13 to +140 degrees F
Shipping and storage temperature (product
packed in factory packing)
10 degrees C per hour18 degrees F per hour
Temperature shock immunity (maximum rate of
temperature change)
Humidity
Protect the disk array from excessive humidity. You should not observe condensation in or around the
product under any conditions. There is no procedure for recovery from moisture condensation.
Table 5 Humidity specifications
Non-condensing relative humidity (RH)Humidity range type
20% to 80%
Operating humidity range at 22 degrees C (71
degrees F)
8% to 90%Non-operating humidity range
5% to 95%
Shipping and storage humidity range (product
packed in factory packing)
26 degrees C (79 F)Operating maximum wet bulb temperature
XP10000 Disk Array Owner's Guide 31