HP StorageWorks Virtual Array 7000 Family User and Service Guide (January 2005)
Table Of Contents
- Warranty Information
- Product Overview
- System Configurations
- Lowest Entry Point, Non-HA Minimum Configuration (VA 7100 only)
- Lowest Entry Point, Non-HA Minimum Configuration (VA 7410)
- Entry Level Non-Cluster With Path Redundancy (All VA arrays)
- Entry Level Cluster with Path Redundancy High Availability (VA 7410)
- Midrange Non-Cluster (All VA arrays)
- Midrange Non-Cluster (VA 7410)
- Midrange Non-Cluster with Full Storage Path Redundancy (All VA Arrays)
- Typical Non-Clustered with Path Redundancy (VA 7410)
- Typical Clustered Configuration (All VA models)
- Typical Clustered Configuration (VA 7410)
- HP-UX MC Service Guard or Windows 2000 Cluster (All VA arrays)
- Highly Redundant Cluster (VA 7410)
- Typical Highly Redundant Cluster (All VA models)
- Typical Highly Redundant Cluster (VA 7410)
- Troubleshooting
- Servicing & Upgrading
- Specifications & Regulatory Statements

Specifications & Regulatory Statements 141
Specifications & Regulatory
Statements
Table 29 Controller & Disk Enclosures Electrical Specifications
*Current rating is with 2 inputs
Electrical
Parameter
Controller Enclosure Disk Enclosure
Voltage
(Auto-Ranging)
100-127 Vac;
200-240 Vac
100-127 Vac;
200-240 Vac
Current
(Maximum)*
6.85 A @ 100 Vac;
5.71 A @ 120 Vac;
3.43 A @ 200 Vac;
2.98 A @ 230 Vac
4.8 A @ 100 Vac;
4.0 A @ 120 Vac;
2.3 A @ 200 Vac;
2.1 A @ 230 Vac
Frequency 50/60 Hz 50/60 Hz
Inrush Current
(Peak)
36 A 17.5 A
Power
Consumption
670 W 500 W
Heat
Dissipation
2288 BTU/hr 1611 BTU/hr
VA
Rating
685 VA 500 VA