HP StorageWorks Scalable File Share for SFS20 Enclosure Hardware Installation Guide Version 2.2

Figure 2-20 Group of Three Power Strips
CAUTION: Do not use the power strips to supply power to any components not already
configured into the cluster. This could cause a power overload.
!
zk-2071
Each PDU is connected to a separate circuit-breaker-protected, AC site power source (220-240
VAC ±10%, 50 or 60 Hz ± 5%).
The 24-amp PDU power cord has a NEMA L6-30P, 3-wire, 30-amp, 60-Hz connector. The NEMA
L6-30R wall receptacle is shown in Figure 2-21 “NEMA L6-30R Wall Receptacle”.
Figure 2-21 NEMA L6-30R Wall Receptacle
The 32-amp PDU power cord has an IEC 309-32 A, 3-wire, 32-amp connector. The IEC309-32
wall receptacle is shown in Figure 2-22 “IEC 309 Wall Receptacle”.
Figure 2-22 IEC 309 Wall Receptacle
The PDU power cords of the three PDUs should be connected to separate building power sources
to ensure no single point of failure (NSPOF) for the power distribution system.
2.7 Cables
The following cables are used in an HP SFS for SFS20 Enclosure configurations:
2.7 Cables 63