zl Power Supply Shelf Installation and Getting Started Guide 2009-06

2-4
Installing and Connecting the External Power Supply Shelf
Installation Procedures
Installing and Connecting the External
Power Supply Shelf
1. Prepare the Installation Site
Cabling - Only use the EPS cables supplied with the unit for external
power connections to switches.
Installation Location - Before installing the unit, plan its location and
orientation relative to other devices and equipment:
In both the front and back of the unit, leave at least 7.6 cm (3 inches)
of space for the EPS cables, and the power cord.
On the sides of the unit, leave at least 7.6 cm (3 inches) for cooling.
2. Mount the Unit
The Power Supply Shelf can be mounted in these ways:
in a rack or cabinet
on a horizontal surface
Rack or Cabinet Mounting
The Power Supply Shelf is designed to be mounted in any EIA-standard 19-
inch telco rack or communication equipment cabinet. The mounting brackets
have multiple mounting holes and can be rotated allowing for a wide variety
of mounting options.
WARNING For safe operation, please read the installation precautions on
page 2-3, before mounting the unit.
Equipment
Cabinet
Note
The 12-24 screws supplied with the unit are the correct threading for standard
EIA/TIA open 19-inch racks. If you are installing the unit in an equipment
cabinet such as a server cabinet, use the clips and screws that came with the
cabinet in place of the 12-24 screws that are supplied with the unit.
1. Use a #1 Phillips (cross-head) screwdriver and attach the mounting
brackets to the unit with the included 8-mm M4 screws. The screws must
be tightened sufficiently to provide proper support for the unit in the rack.