62 Error messages
CM-EVENT_TEMPERATURE_SHUTDOWN
Message
Probable cause
At least two temperature sensors have crossed the shutdown temperature threshold. Temperature problems
usually indicate problems with fans or the environment temperature.
Recommended action
1. Wait until the switch has cooled down before rebooting and running diagnostics.
2. Use the tempShow command to view the temperature of the MP Router.
3. Use the fanShow command to verify that the fans are operating properly.
4. Replace any defective fan FRUs.
5. Verify that the room temperature is within the operational range.
See the installation guide for your switch for details about the operational temperature range.
Severity
Critical
CM-EVENT_USER_LOGIN_SUCCESS
Message
Probable cause
An admin or user has successfully logged in to the MP Router.
Recommended action
No action is required.
Severity
Info
CM-EVENT_USER_LOGOUT
Message
Probable cause
An admin or user has logged out of the MP Router.
process_id (EvtMgr): date time
Critical CM-EVENT_TEMPERATURE_SHUTDOWN, 1, Switch shutdown due to shutdown
temperature exceeded
process_id (EvtMgr): date time
Info CM-EVENT_USER_LOGIN_SUCCESS, 4, User login: login_level
process_id (EvtMgr): date time
Info CM-EVENT_USER_LOGOUT, 4, User login: login_level