Installation Instructions hp StorageWorks SAN Switch Rack Mount Kit Fourth Edition (September 2004) Part Number: AV–RU6YD–TE This document provides step-by-step installation instructions for using the SAN Switch Rack Mount Kit with the following specific HP branded racks: HP 9000 Series Rack, HP 10,000 Series Rack and HP System/e Rack. For the latest version of these Installation Instructions and other documentation, access the HP storage website at: http://www.hp.com/country/us/eng/prodserv/storage.
© Copyright 2004 Hewlett-Packard Development Company, L.P. Hewlett-Packard Company makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.
About this Document This document describes how to use the optional SAN Switch Rack Mount Kit to install the following HP StorageWorks Storage Area Network (SAN) devices: ■ Multi-protocol (MP) Router ■ SAN Switch 2/8V ■ SAN Switch 2/16, SAN Switch 2/16V or SAN Switch 2/16N ■ SAN Switch 2/32 Note: The HP StorageWorks SAN Switch Rack Mount Kit is for use with the HP 9000 Series, HP 10,000 Series, and HP System/e racks only.
Rack Stability Rack stability protects personnel and equipment. WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: ■ The leveling jacks are extended to the floor. ■ The full weight of the rack rests on the leveling jacks. ■ In single rack installations, the stabilizing feet are attached to the rack. ■ In multiple rack installations, the racks are coupled. ■ Only one rack component is extended at any time.
Installation and Safety Guidelines Read the following sections for installation guidelines.
Using the SAN Switch Rack Mount Kit to Install an HP StorageWorks Device Read this section to install a SAN Switch or MP Router in an HP Series 9000, HP Series 10,000, or HP System/e rack. Note: The SAN Switch Rack Mount Kit installation requires one technician. The following items are required to install the device in a rack: ■ The HP StorageWorks MP Router or specific HP StorageWorks SAN Switch listed in the About this Document section on page 3.
Table 1: Rack Mount Kit Rails and Rail Mounting Hardware (Continued) Item Description (14) 8-32 x 5/16-inch Phillips pan-head SEMS screws for use with the MP Router, SAN Switch 2/8, SAN Switch 2/8V, SAN Switch 2/16, SAN Switch 2/16V and SAN Switch 2/16N.
To install the HP StorageWorks device in a rack: 1. Check the contents of the shipping carton to verify that all the required parts and hardware are available. 2. Choose a mounting location in the rack. 3. Attach the rear mounting brackets to the rear rack uprights by completing one of the following steps: — For an HP 10,000 Series rack, assemble each of the two brackets with two #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and two #10 adapter washers as shown in Figure 1.
— For an HP System/e rack, install each of the two rear mounting brackets with two #10-32 x 1/2-inch Phillips pan-head screws and two #10 alignment washers as shown in Figure 2. Figure 2: Installing the Rear Mounting Brackets (HP System/e Rack-Left Rear Upright) Note: This kit contains both left rails and right rails. The rails are labelled Right and Left.
4. Assemble the outer rails by completing the following steps: a. Attach the left outer rail and the right outer rails to the rear mounting brackets using two 1/4-20 hex nuts with captive star lock washers. Attach the hex nuts loosely (as shown in Figure 3). Do not tighten; tighten the hex nuts later in step 12 on page 17.
b. Depending on the rack you are using, complete one of the following tasks: — For an HP 10,000 Series rack, install two #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and two #10 adapter washers in the upper and lower hole locations of the right rail. Then install two #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and two #10 adapter washers in the upper and lower hole locations of the left rail, as shown in Figure 4.
— For an HP System/e rack, install two #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and two #10 alignment washers in the upper and lower hole locations of the right rail. Then install two #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and two #10 alignment washers in the upper and lower hole locations of the left rail, as shown in Figure 5.
5. The SAN Switch Rack Mount Kit provides different screw types for securing the inner rails. Specific devices require a different number of these screws. Determine the number of screws to attach the inner rails to the device as follows: Caution: Do not use any other screws other than the ones provided. Use of any longer lengths can cause damage to internal components. a.
0012a.eps Figure 6: Attaching the Inner Rails to a SAN Switch 2/16V E OL NS CO 1 MT MG 2 MT MG ITY TIV SP 14 13 12 11 9 AC D EE 15 K LIN D EE SP E /Gb CT FC K/A LIN 10 8 7 6 5 4 63 3 C 0 VA 2 6.0 A 47- Hz -24 100 1 0 AC DC OK OK R WE PO S RT PO STEM SY 63 C 0 VA 6.0 A 47- Hz -24 100 AC DC OK OK 25007a.
Note: For factory integration only, tighten the #8-32 x 3/16-inch Phillips pan-head screw with thread lock and torque between 6 to 8 inch-pounds. 8. Verify that a plenum is installed on the SAN Switch 2/8V, SAN Switch 2/16, SAN Switch 2/16V or SAN Switch 2/16N models only, as shown in Figure 8. The plenum is an overlay that dissipates the heat generated by the switch, and is necessary to prevent overheating.
Note: For the SAN Switch 2/8V, 2/16V or 2/16N, a plenum is required when the switch is installed in an HP 9000 Series, HP 10,000 Series or HP System/e rack. The SAN Switch 2/16 model uses a shorter version of the plenum (part number A7346-00001). The SAN Switch 2/8V, SAN Switch 2/16V and SAN Switch 2/16N models use a longer version of the plenum (part number 5697-4919). 10. Insert the switch with the attached inner rails into the outer rails.
Figure 10: Securing the Device (in an HP System/e rack) 12. Tighten the hex nuts installed in step 4 on page 10. See Figure 3. Note: To uninstall a device, remove the middle #10-32 x 1/2-inch Phillips pan head screw with captive star lock washer from either side of the rack uprights.