HP StorageWorks ESL E-Series Tape Library users guide (350799-010, October 2007)
Sense
key
ASC ASCQ
Messag e name / description
5
87 F0
DEPTH INVALID COMMAND
Depth hardware commanded to position out of system mechanical limits.
• Run the Robotics to Home Position test from the OCP.
• If the problem persists, c alibrate the library.
• Verify that the host software application is supported, has up-to-date
patches, and is correctly confi gured.
• Verify that the library and its components have the current firmw are.
5
1A 00
PARAMETER LIST LENGTH ERROR
Invalid parameter list length field specified by command.
• Verify that the host software application is supported, has up-to-date
patches, and is correctly confi gured.
• Verify that the library and its components have the current firmw are.
5
2C 00
COMMAND SEQUENCE ERROR (read of unwritten echo buffer)
5
3A
00
MEDIUM NOT PRESENT
The inventory indicated that a cartridge was in this bin but no cartridge
was sensed by the picker when it at tempted to pick it. It may also
indicatethatthetapeisnotreadytobepickedfromthedrivebecause
thetapeisnotfullyunloaded.
• Retry the command.
• Check for proper seating of the car tridge.
5
3B 0D
MEDIUM DESTINATION ELEMENT FULL
Destination element address already contains a cartridge.
• Re-inventory the cabinet and retry the move command using your
application software.
• If the problem recurs, run the Robotics to Home Position test followed
by a cabinet inventory, and retry the move command using your
application software.
5
3B 0E
MEDIUM SOURCE ELEMENT EMPTY
Source element address does not contain a cartridge.
• Re-inventory the cabinet and retry move command using your
appli
cation software.
• If th
e problem recurs, run the Robotics to Home Position test followed
by a c
abinet inventory, and retry the move command using your
application software.
5
4E
00
OVERLA PPED COMMANDS ATTEMPTED
Due to a second command being sent from the same host before a
previous command has completed, the previous command has been
aborted. This may also occur when executing off-line commands via the
control panel and DIAG port simultaneously.
• Verify that the host software application is supported, has up-to-date
patches, and is correctly confi gured.
• Verify that the library and its components have the current firmw are.
5
8A
02
UNCALIBRATED POSITION
System requires calibration. Run the Calibrate Cabinet test from the OCP.
5
8B E0
CLM INVALID START CONDITION
CLM hardware condition is unknown. Run the Robotics to Home Position
test.
HP StorageWorks
119