HP StorageWorks ESL E-Series Tape Library Pre-installation Site Survey (358836-003, September 2007)
1
4
6
5
2
3
11033
1
Back door clearance—28 inches (71 cm)
2
Depth of ca
binets—50 inches (127 cm)
3
Front door clearance—23 inches (58 cm)
4
Width of cabinets—30 inches (76 cm) per C LM library cabinet
5
Space bet
ween cabinets—1 inch (2 .5 cm)
6
Clearance left of primary cabinet—52 inches (130 cm) used
during installing and servicing the CLM library
Figure 2 Floor spa ce requirements (CLM libraries)
• The tape library is rated: 200-240VAC, 50-60Hz, 8A, 1600W.
• Library
power requirements may require modi fic a tion of the facility’s existing power capabilities
by a qua
lified electrician. The required wall outlet for the United States and Canada is shown in
Figure 3 on page 4. The dedicated outlet and a 20 amp circuit breaker must provide power to
one library only. Outside North America, replace the supplied power cord with a harmonized 3
x1.5mm
2 power cord that is approved by the c ountry where used, and install the appropriate
wall outlet. For a listing of power cords available from H P, see the product QuickSpecs available
from h
ttp://www.hp.com/go/auto mated.
pre-installation site survey