HP StorageWorks ESL E-Series tape library pre-installation site survey (358836-003, October 2007)
Site ready crite
ria
Yes No
N/A
Installation re
quirements
10. For LTO2 and LTO3 tape drives, is th e correct number of HP StorageWorks
E2400-160 Fibre Channel interface controllers available or on order (one FC controller
for every four tape drives)?
11. For LTO4 tape drives, is the correct number of ports available on an FC switch in
your SAN (one port for every LTO4 tape drive)?
12. Has the equipment location/arrangement been planned? (power
source/host
/library/cabling).
13. Is service a nd traffic clearance provided (ceiling height/sprinkler heads/cable
racks)? Refer to the Site Requirement section of the unpacking instructions for floor
space requirements).
14. For a CLM library, is there enough room for all of the cabinets, 1 inch of space
between the cabinets, and 52 inches (130 cm) of clear space to the left of the primary
cabinet (as you face the front of the library)?
15. AreFibreChannelcablesavailableoronorder?
16. Are there two dedicated power sources with the correct outlets available? (See
“Library power requirements” on page 3.) The library has standard redundant power
supplies.
17. Are the power cords supplied (NEMA 6-20 plug) adequate for this installation? (If
not, please refer to “Library power requirements” on page 3.)
18. IfthelibraryisconnectedtoaUPS,isabypassswitchplanned?
19. Is emergency power-off capability provided?
20. Is the power disconnect (breaker panel or bypass switch) located within sight of the
library? (This is a National Electric Code requirement).
21. Are th
e temperature, humidity, and airborne contamination at the installation site
control
led?
22. Has a qualified application backup software been installed on the host? (Please
refer to the product QuickSpecs for software compatibility information.)
23. Has access to the customer site been provided to complete this survey?
NOTE:
If any survey questions are answered "No", there may be a delay in librar y shipment. Please refer
to Table 9.