FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Edge Switch 2/24 Service Manual (AA-RTDXC-TE, July 2004)
Diagnostics
63Edge Switch 2/24 Service Manual
■ Perform the data collection procedure as part of FRU removal and
replacement.
■ If multiple power supply failures occurred, connect the switch to facility AC
power after both power supplies are replaced.
Caution: Do not remove a power supply unless a replacement FRU is
immediately available. To avoid product overheating, a removed power supply
must be replaced within five minutes.
Did fan module (power supply) replacement solve the problem?
NO YES
↓ The switch appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
7
A power supply failed POSTs (as indicated by FRU code 06) and must be
removed and replaced. Refer to “RRP: Redundant Power Supply” on page 198.
■ This procedure is concurrent and can be performed while switch power is on.
■ Perform the data collection procedure as part of FRU removal and
replacement.
■ If multiple power supply failures occurred, connect the switch to facility AC
power after both power supplies are replaced.
Caution: Do not remove a power supply unless a replacement FRU is
immediately available. To avoid product overheating, a removed power supply
must be replaced within five minutes.
Did power supply replacement solve the problem?
NO YES
↓ The switch appears operational. Exit MAP.
Contact the next level of support. Exit MAP.