FW 08.01.00 McDATA Sphereon 4500 Fabric Switch Installation and Service Manual (620-000159-330, November 2005)

3-26
McDATA Sphereon 4500 Fabric Switch Installation and Service Manual
Maintenence Analysis Procedures
1
Table 3-8 lists event codes, explanations, and MAP steps.
2
Visual inspection (amber LED illuminated) or event code 300, 301,
302, 303, 304, or 305 indicates one or more cooling fans failed, and
one or both power supplies (combined FRUs) must be removed and
replaced. Refer to RRP 2: Redundant Power Supply.
The procedure is concurrent and performed while the product is
operational.
If multiple fan failures caused a thermal shutdown, connect the
product to facility AC power after power supply(s) are replaced.
Table 3-8 MAP 400 Event Codes
Event
Code
Explanation Action
300 Cooling fan propeller failed. Go to step 2.
301 Cooling fan propeller failed. Go to step 2.
302 Cooling fan propeller failed. Go to step 2.
303 Cooling fan propeller failed. Go to step 2.
304 Cooling fan propeller failed. Go to step 2.
305 Cooling fan propeller failed. Go to step 2.
370 Cooling fan status polling temporarily disabled. Go to step 3.
426 Multiple ECC single-bit errors occurred. Go to step 4.
433 Non-recoverable Ethernet fault. Go to step 5.
440 Embedded port hardware failed. Go to step 5.
810 High temperature warning (CTP thermal sensor). Go to step 6.
811 Critically hot temperature warning (CTP thermal sensor). Go to step 6.
812 CTP card shutdown due to thermal violations. Go to step 6.
850 Switch shutdown due to CTP thermal violations. Go to step 6.