FW 08.01.00 McDATA Sphereon 4500 Fabric Switch Installation and Service Manual (620-000159-330, November 2005)

3-14
McDATA Sphereon 4500 Fabric Switch Installation and Service Manual
Maintenence Analysis Procedures
2
As indicated by event code 400, POST/IPL diagnostics detected a
FRU failure.
a. At the Event Log, examine the first two bytes of event data.
b. Byte 0 specifies failed FRU. Byte 1 specifies the slot number of
the failed FRU (00 for nonredundant, 00 or 01 for redundant) as
listed in Table 3-6.
3
A fan module or power supply failed POSTs and the power supply
(containing the fan, if applicable) must be removed and replaced.
Refer to RRP 2: Redundant Power Supply.
The procedure is concurrent and performed while the product is
operational.
If multiple fan failures caused a thermal shutdown, connect the
product to facility AC power after power supply(s) are replaced.
Perform a data collection as part of FRU removal and
replacement. Refer to Collect Maintenance Data (EFCM Basic
Edition) or Collect Maintenance Data (Element Manager).
NOTE: Do not remove a power supply unless a replacement FRU is
available. To avoid product overheating, a removed power supply must be
replaced within five minutes.
Was the maintenance action successful?
NO YES
The product is operational. Exit MAP.
Contact the next level of support. Exit MAP.
Table 3-6 MAP 200 Byte 0 FRU Codes
Byte 0 Failed FRU Action
02 CTP card. Replace the switch. Exit MAP.
05 Fan module. Go to step 3.
06 Power supply. Go to step 3.