FW 07.00.00/HAFM SW 08.06.00 McDATA Sphereon 4500 Fabric Switch Installation and Service Manual (620-000159-320, April 2005)
Diagnostics
4-47
8. Click Close to close the dialog box.
9. Remove the diskette with the newly-collected maintenance data
from the browser PC floppy drive. Return the diskette with the
failed FRU to McDATA for failure analysis.
Management
Server
To collect maintenance data (retrieve the dump file from the
management server hard drive) from the Sphereon 4500 Element
Manager application:
1. At the management server, open the SAN management
application (SANavigator 4.0 or EFCM 8.0).
2. At the SAN management application’s physical map, right-click
the product icon representing the switch for which the data
collection procedure is to be performed, then select Element
Manager from the pop-up menu. The application opens.
3. Select the Data Collection option from the Maintenance menu. The
Save Data Collection dialog box displays (Figure 4-30).
Figure 4-30 Save Data Collection Dialog Box
4. Remove the backup CD from the management server’s compact
disk-rewritable (CD-RW) drive and insert a blank rewritable CD.