Verify redundant power supply operation.
a. Inspect the power supply and ensure the amber LED is
extinguished.
b. At the management server’s Hardware View (Figure 3-10 on
page 3-20), observe the graphic representing the power supply
and ensure a failure symbol (blinking red and yellow diamond)
does not appear.
Is a failure indicated?
YES NO
The switch appears operational. Exit MAP.
8
Visual inspection or an event code 200 or 201 indicates one or both
power supplies must be removed and replaced. Refer to RRP 2:
Redundant Power Supply on page 5-6.
This procedure is concurrent and can be performed while switch
power is on.
Perform the data collection procedure as part of FRU removal
and replacement.
If multiple power supply failures occurred, connect the switch to
facility AC power after both power supplies are replaced.
ATTENTION ! Do not remove a power supply unless a replacement FRU is
immediately available. To avoid product overheating, a removed power
supply must be replaced within five minutes.
Did power supply replacement solve the problem?
NO YES
The switch appears operational. Exit MAP.
Contact the next level of support. Exit MAP.