McDATA Sphereon 4500 Fabric Switch Installation and Service Manual
MAP 0100: Power Distribution Analysis
This MAP describes fault isolation for the switch power distribution
system, including defective AC power cords or redundant power
supplies.
1
Was an event code 200 or 201 observed at the SANpilot event log or
at the Sphereon 4500 Event Log (management server)?
YES NO
↓ Go to step 9.
2
Table 3-4 lists event codes, brief explanations of the codes, and the
associated steps that describe fault isolation procedures.
3
Have the customer inspect and verify that facility power is within
specifications. These specifications are:
• One single-phase connection for each power supply.
• Input power between 100 and 240 VAC, and at least 5 amps.
• Input frequency between 47 and 63 Hz.
Is facility power within specifications?
YES NO
↓ Ask the customer to correct the facility power problem. When
facility power is corrected, continue to the next step.
Table 3-4 MAP 100 Event Codes
Event
Code
Explanation Action
200 Power supply AC voltage failure. Go to step 3.
201 Power supply DC voltage failure. Go to step 3.