FW 07.00.00/HAFM SW 08.06.00 McDATA Sphereon 4300 Fabric Switch Installation and Service Manual (620-000171-010, April 2005)

Diagnostics
3-33
NO YES
Go to step 1.
The switch appears operational. Exit MAP.
9
Is the green PWR LED illuminated, the amber ERR LED illuminated,
and all Fibre Channel traffic disrupted (not operational)?
NO YES
A CTP card failure is indicated. Replace the switch.
Exit MAP.
Analysis for this failure is not described in this MAP. Go to MAP 0000:
Start MAP on page 3-6. If this is the second time at this step, contact
the next level of support. Exit MAP.
10
An event code 426 (SDRAM problem), 810 (high-temperature
warning), or 811 (critically-hot temperature warning) indicates an
intermittent problem that may result in switch failure.
Is the appearance of this event code a recurring problem?
NO YES
A CTP card failure is indicated. Replace the switch.
Exit MAP.
Perform the data collection procedure and contact the next level of
support. Refer to Collect Maintenance Data on page 4-22. Exit MAP.
11
An event code 433 or 440 indicates a CTP card failure. Replace the
switch. Exit MAP.
12
Does the SANpilot interface appear operational?
NO YES
Go to step 14.
13
A Page cannot be found, Unable to locate the server, HTTP
404 - file not found, or other similar message appears. The message
indicates the PC cannot communicate with the switch because: