FW 07.00.00/HAFM SW 08.06.00 McDATA Sphereon 4300 Fabric Switch Installation and Service Manual (620-000171-010, April 2005)

3-32
McDATA Sphereon 4300 Fabric Switch Installation and Service Manual
Does the switch appear powered on?
YES NO
An AC power distribution or CTP card failure is indicated. Go
to MAP 0000: Start MAP on page 3-6. If this is the second
time at this step, replace the switch. Exit MAP.
5
Inspect cooling fans at the rear of the switch to ensure all fan blades
are rotating.
Does cooling fan inspection indicate a failure (one or more cooling
fans not rotating)?
YES NO
Go to step 7.
6
Visual inspection or an event code 300, 301, or 302 indicates one or
more cooling fans failed. Replace the switch. Exit MAP.
7
Inspect the switch front panel.
Is the green PWR LED illuminated and the amber ERR LED
illuminated and blinking (beaconing)?
YES NO
Go to step 9.
8
Unit beaconing is enabled for the switch.
a. Consult the customer and next level of support to determine the
reason unit beaconing is enabled.
b. Disable unit beaconing at the SANpilot interface.
1. At the View panel, select Operations at the left side of the
panel. The Operations panel opens with the Switch and
Beacon pages displayed.
2. Click Deactivate to disable beaconing. The message Your
changes have been successfully activated appears.
Was unit beaconing enabled because a failure or degradation was
suspected?