FW 07.00.00/HAFM SW 08.06.00 McDATA Sphereon 4300 Fabric Switch Installation and Service Manual (620-000171-010, April 2005)

3-18
McDATA Sphereon 4300 Fabric Switch Installation and Service Manual
Were one or more event codes found?
YES NO
Perform fault isolation at the switch. Go to step 20.
Go to Table 3-3 on page 3-3 to interpret event codes. Exit MAP.
MAP 0100: Power Distribution Analysis
This MAP describes fault isolation for the switch power distribution
system, including a defective AC power cord or power supply.
1
Is fault isolation being performed at the switch?
YES NO
Fault isolation is being performed at the SANpilot interface.
Go to step 8.
2
Verify the switch is connected to facility power and is powered on.
a. Ensure the AC power cord is connected to the rear of the switch
and a facility power receptacle. If not, connect the cord as
directed by the customer.
b. Ensure the associated facility circuit breaker is on. If not, ask the
customer to set the circuit breaker on.
c. Ensure the AC power cord is not damaged. If damaged, replace
the cord.
Was a corrective action performed?
YES NO
Go to step 4.
3
Verify power supply and switch operation. Inspect the switch for
indications of being powered on, such as:
At the front bezel, an illuminated PWR LED (green)
or ERR LED (amber).
Illuminated LEDs adjacent to Fibre Channel ports.
Audio emanations and airflow from cooling fans.