HP StorageWorks Fabric OS 5.X Diagnostics and System Error Messages Reference Guide (AA-RVHZB-TE, September 2005)
120 Error messages
Probable Cause
Indicates that a blade in the specified slot or the switch (for nonbladed switches) is being shut down for
environmental reasons; its temperature or voltage is out of range.
The FRU ID value is composed of a FRU type string and an optional number to identify the unit, slot, or
port. The FRU ID value can be:
• Switch for fixed port count switches.
• Slot 1 through Slot 10 for the Core Switch 2/64, SAN Director 2/128, and 4/256 SAN Director.
Recommended Action
Check the environment and make sure the room temperature is within the operational range of the switch.
Use the fanShow command to verify fans are operating properly. Make sure there are no blockages of
the airflow around the chassis. If the temperature problem is isolated to the blade itself, replace the blade.
Voltage problems on a blade are likely a hardware problem on the blade itself; replace the blade.
Severity
CRITICAL
EM-1006
Message
Probable Cause
Indicates that the sensors show the voltage is below minimum limits. The switch or specified blade is being
shut down for environmental reasons; the voltage is too low.
Recommended Action
If this problem occurs on a blade, it usually indicates a hardware problem on the blade; replace the blade.
If this problem occurs on a switch, it usually indicates a hardware problem on the main board; replace the
switch.
Severity
CRITICAL
EM-1007
Message
Probable Cause
Indicates that the voltage on a switch has exceeded environmental limits. A reset is sent to the faulty slot or
the switch for nonbladed switches.
Recommended Action
There is most likely a voltage hardware problem on the blade or motherboard of the switch.
For the Core Switch 2/64, SAN Director 2/128, and 4/256 SAN Director, replace the blade FRU.
For the SAN Switch 2/32 and SAN Switch 4/32, replace the motherboard FRU.
<timestamp>, [EM-1006], <sequence-number>,, CRITICAL,
<system-name>, <FRU Id> has faulted. Sensor(s) below minimum limits
<timestamp>, [EM-1007], <sequence-number>,, CRITICAL,
<system-name>, <FRU Id> is being reset. Sensor(s) has exceeded max
limits