Site Preparation Guide, Second Edition - HP rp8400 Server Series
Appendix A
System Requirements Summary
Power Consumption and Air Conditioning Requirement
47
Power Consumption and Air Conditioning Requirement
Table A-3 Example Power Consumption (Typical) and Air Conditioning
Requirement Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 330 330.00 (0.33) 0.094
Cell Board (PA8700) 4 500 2000.0 (2.00) 0.569
PCI Card (25W max) 16 10 160.00 (0.16) 0.045
Power Supply (BPS) 6 49 294.00 (.294) 0.084
DVD 2 20 40.00 (0.04) 0.011
Disk Drive 2 25 50.00 (0.05) 0.014
Core I/O 2 29 58.00 (0.058) 0.016
PCI Power Supply 2 47 94.00 (0.094) 0.027
Total 3026.00 (3.026) 0.860
Table A-4 Power Consumption (Typical) and Air Conditioning Requirement
Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 330 330.00 (0.33) 0.094
Cell Board (PA8700) 500
PCI Card (25W max) 10
Power Supply (BPS) 49
DVD 0
Disk Drive 25
Core I/O 29
PCI Power Supply 47
Total