Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440

System Specifications
Electrical Specifications
Chapter 1
17
Table 1-5 list maximum and typical power requirements for the HP 9000 rp4410 and HP 9000 rp4440
servers. These tables provide information to help determine the amount of AC power needed for your
computer room.
Power and Cooling
Typical power consumption and cooling values for HP 9000 rp4410 and HP 9000 rp4440 servers are listed in
Table 1-6. The table lists power and cooling values associated with servers which contain the listed
components. These power and cooling values are considered typical and not maximum for the configurations
shown.
Table 1-5 System Power Requirements
Power Required (50-60 Hz) Watts VA Comments
Maximum configuration
a
a. Maximum power is the sum of the worst case power consumption values of every subsystem in your
HP 9000 rp4410 or HP 9000 rp4440 server. These worst case values should be used to calculate the
worst case power consumption for your facility installation.
1368 1440 Maximum theoretical
Typical configuration
b
b. Typical power consumption values were measured while running power intensive applications.
These values are generally lower than maximum power numbers because all the subsystems in
your HP server rarely draw maximum power simultaneously and for long durations.
1065 1125 Typical
Table 1-6 Typical Configuration Power Values
CPU
Qty
Memory
Gigabytes
PCI Cards
(assuming
10W each)
DVDs
Hard
Disk
Drives
Core
I/O
Bulk
Power
Supplies
Typical
Power-
Watts
Typical
Cooling-
BTU/Hr
11 GB
(4 DIMMs @
256 MB ea.)
0 0 1 2 2 410 1399.74
2
32 GB
a
(32 DIMMs @
1 GB ea.)
b
0 0 1 1 1 540 1843.56
2
32 GB
a
(32 DIMMs @
1 GB ea.)
b
6 1 2 2 2 700 2389.80
4
32 GB
a
(32 DIMMs @
1 GB ea.)
b
0 1 2 2 2 895 3055.53