HP StorageWorks XP24000/XP20000 Disk Array Site Preparation Guide (AE002-96055, September 2010)
415
VAC
50 Hz
only
400
VAC
50 Hz
only
380
VAC
50 Hz
only
240
VAC
50 Hz
only
230
VAC
50 or
60 Hz
220
VAC
50 Hz
only
208
VAC
60 Hz
only
200
VAC
50 or
60 Hz
Parameter
22222222
Number of
power cords
3030303030303030
Recommended
circuit breakers
(amps)
22222222
Number of cir-
cuit breakers
Table 20 DKU power specifications, 50-amp, 50 or 60 Hz, single-phase
240 VAC 50
Hz only
230 VAC 50
or 60 Hz
220 VAC 50
Hz only
208 VAC 60
Hz only
200 VAC 50
or 60 Hz
Parameter
221212202191184
Minimum
operating
voltage
(VAC)
254244233220212
Maximum
operating
voltage
(VAC)
14.815.516.217.217.8
Rated line cur-
rent per power
cord (Amps rms)
22222
Number of
power cords
5050505050
Recommended
circuit breakers
(amps)
22222
Number of cir-
cuit breakers
Table 21 DKU power specifications, 30-amp, 50 or 60 Hz, single-phase
240 VAC 50
Hz only
230 VAC 50
or 60 Hz
220 VAC 50
Hz only
208 VAC 60
Hz only
200 VAC 50
or 60 Hz
Parameter
221212202191184
Minimum
operating
voltage
(VAC)
XP24000/XP20000 Disk Array Site Preparation Guide 47