HP StorageWorks XP24000/XP20000 Disk Array Site Preparation Guide (AE002-96055, September 2010)

Full array
(1 DKC and 4 DKUs)
Each DKUDKCParameter
1076232140621997Max. BTUs per hour
2712053945543Max. kcal per hour
Table 11 XP20000 maximum heat and power specifications
Full arraySecond RackPrimary RackParameter
7.23.04.2Power consumption (kVA)
6.92.94.0Heat dissipation (kW)
23490978813702BTUs per hour
591924673453Kcal per hour
Table 12 shows the disk array's air flow requirements.
Table 12 Air flow specifications XP24000/XP20000 Disk Arrays
Air flow (cubic meters/minute)DescriptionProduct number
34
HP XP24000 Disk Control Frame
(DKC)
AE131A
32
HP XP24000 Disk Array Frame
(DKU)AE173A
4.3
HP XP20000 DKC Disk Control
Unit
AE191A
1.3HP XP20000 SVP/Battery ChassisAE194A
5HP XP20000 Disk ChassisAE196A
Cooling airflow for the XP24000 is air intake at front and rear and hot air exhaust out the top.
Therefore, the XP24000 is not suitable in a hot isle containment system.
XP20000 cooling airflow has air intake at front and hot air exhaust out the rear. Therefore, the
XP20000 is suitable in hot isle containment system.
Controlling dust and pollution
Airborne contaminants and particles of a certain size and hardness can damage the system. Some
of the most common contaminants are dust, smoke, ash, corrosive gases and corrosive particulate.
Mechanical filters on the disk array protect it by trapping large dust particles. Smaller particles can
pass through most filters, and can eventually cause problems in mechanical parts and electrical
contacts. Prevent small dust particles from entering the computer room by maintaining its air conditioning
system at a high static air pressure level.
Your HP representative can help you determine if you need to be concerned about airborne
contaminants including gaseous chemical contaminants. HP strongly recommends your site be evaluated
for metallic particulate contamination and gaseous chemical contaminants for sites with suspect air
quality concerns. Evaluation should be done before the system is installed and periodically monitored.
Site requirements for the HP Disk Arrays36