HP Rack and Power Manager User Guide

Operation
To manually restart a load segment or UPS that remained off after a shutdown:
1. From the Affects dropdown box, select the component you want to restart in the Restart
UPS box.
2. Click Apply to restart the component.
IMPORTANT: If you use the Remain Off option to shut down a load segment to which the
Management Server is attached or to which a server with a Serial Relay Agent installed is attached, you
will not be able to restart the UPS with HP Rack and Power Manager. To recover, gracefully shut down
the remaining servers on the active load segments of the UPS. Manually power down the UPS using
the power button on the UPS, then reapply power to the UPS.
Agents Tab
Click the Agents tab in the top frame to view the Managed Agents screen.
5-40 HP Rack and Power Manager User Guide