HP Rack and Power Manager User Guide
Operation
After entering information in the Device Properties box, do one of the following:
•
•
Click Apply at the bottom of the screen to accept the information that has been entered.
Click Undo Changes to reject all changes and keep the box open.
Table 5-3: CMC Device Properties
Table Item Comments
Device Name Enter the name of the CMC to aid in identification when sending alert
messages and viewing from the console.
Device Location Select the physical location of the CMC to aid in identification when alert
messages are sent.
Temperature Format Select the temperature unit of measure (0° t o 93° C, 32° to 200° F).
Audible Alarm Enable or disable audible alarms.
Enable Local Alarm
Silence Button
Select the checkbox to allow an active audible alarm to be silenced
when the Enter/Alarm Silence button on the CMC front panel is pressed.
New alarm conditions will continue to signal audible alarms after
Enter/Alarm Silence is pressed.
Language Select the language to display on the CMC LCD menu. Available
languages are English, French, Italian, German, Spanish, Dutch, and
Japanese.
SNMP Contact
Information
Enter the user name, e-mail address, or pager number of a person who
can provide direct physical access to the room or building where the
CMC is located in case of an emergency. This person need not have
responsibility for actually maintaining the CMC.
SNMP Read
Community String
Edit the SNMP Read Community string if necessary. The SNMP Read
Community string displayed on the CMC Properties screen must match
that on the CMC device.
IMPORTANT: If you edit the string on this screen, be sure to make the
same change for the CMC device using a terminal emulation program.
SNMP Write
Community String
Edit the SNMP Write Community string if necessary. The SNMP Write
Community string displayed on the CMC Properties screen must match
that on the CMC device.
IMPORTANT: If you edit the string on this screen, be sure to make the
same change for the CMC device using a terminal emulation program.
Device Password
Enter a password for the CMC hardware, and select Enable to activate
the password. Passwords can be no longer than six characters.
Characters can only be capital letters or numbers. If the password is
enabled, the password is required to change the CMC IP address and
settings, using the front panel controls or a terminal program. This
password is different than the login password for HP Rack and Power
Manager, which is set on the My Account screen.