HP Rack and Power Manager User Guide

Operation
Locksets Tabs
Select the Lockset 1 tab to configure the first lockset. Select the Lockset 2 tab to configure
the second lockset. To set each lockset to lock and unlock rack doors:
1. Select Available in the Lock Set Status field for each lockset that is connected to the
CMC. If a lockset that is not connected is shown as available, the CMC will erroneously
detect an alarm condition and send alerts.
2. Click Yes for each rack door that the lock set operates. Each lockset operates two rack
doors.
IMPORTANT: For the door-locking feature to work properly, you must assign at least one intrusion
sensor to each lockset. Refer to “Sensor Setup Screen” in this chapter for information on setting up
the intrusion sensors.
3. Click Yes in the Unlock Upon Event? column to automatically unlock the doors during a
power failure, low battery warning, network failure, or communications failure. Click
Enable Concealed Door Release to be able to manually open locked doors using a
hidden switch. For more information about the concealed door release, refer to the CMC
documentation.
NOTE: HP Rack and Power Manager cannot detect the concealed door release. Be sure that the
concealed door release option is not selected for CMCs that control racks without a concealed door
release.
HP Rack and Power Manager User Guide 5-11
HP CONFIDENTIAL Codename: Swordfish Part Number: 311371-002 Last Saved On: 2/3/04 3:32 PM