HP Rack and Power Manager User Guide

Operation
The sensor entries have additional checkboxes and fields that are used to define setpoints to
which alerts can be associated:
Temperature 1 and 2—Configure the temperature setpoints.
Set the minimum acceptable temperature. The minimum temperature must be within
the 0° to 37° C (32° to 100° F) range.
Set the warning temperature. The warning temperature must be within the
0° to 93° C (32° to 200° F) range.
Set the maximum acceptable temperature. The maximum temperature must be within
the 0° to 93° C (32° to 200° F) range.
NOTE: The Sensor Setup screen displays temperature unit in either °C or °F. Select the unit of
temperature on the CMC Properties screen.
Humidity—Set the minimum and maximum acceptable values. The minimum and
maximum humidity must be within the 0% to 100% range.
Voltage—Set the minimum and maximum acceptable values. The minimum and
maximum voltage must be within the 0 to 255 V range.
Shock—Set the sensitivity of the detector. Enter 10 in this field for maximum
sensitivity; 5 is the default value.
Smoke—Select a checkbox to determine whether the fans are to be turned off and the
rack doors unlocked if the sensor detects smoke.
CAUTION: To minimize potential damage from smoke and fire, HP recommends that
both fans be set to turn off when smoke is detected.
Intrusion x—Use these fields and checkboxes to configure door intrusion.
IMPORTANT: For the door-locking feature to work properly, you must assign at least one intrusion
sensor to each lockset.
a. Type a description of the door in the Labels field.
b. Select an option from the dropdown box to determine which fans, if any, are to be
switched off when the door is opened.
c. Click Disable to disregard the shock sensor alert when the door is opened.
Auxiliary x—Use these fields and checkboxes for any supported detectors connected to
the appropriate input ports on the rear of the CMC. Enter the description of the sensor
type into the text field. For more information about auxiliary sensors, refer to the CMC
documentation.
After entering information on this screen, do one of the following:
Click Apply at the bottom of the screen to accept the information that has been entered.
Click Undo Changes to reject all changes and keep the screen open.
5-8 HP Rack and Power Manager User Guide