HP Apollo a6000 Chassis Setup and Installation Guide

Specifications 42
Specification
HP 2450W Platinum Hot Plug
Redundant Power Supply
HP 2650W Platinum Hot Plug
Redundant Power Supply
Rated input voltage
200 VAC to 208 VAC line to line
3-phase delta
200 VAC to 208 VAC line to line
3-phase delta
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current per
line cord
22.9 A at 200 VAC
22 A at 208 VAC
25 A at 200 VAC
24 A at 208 VAC
Maximum input power per
line cord
7920 VA 8640 VA
Three-phase power (International)
Specification
HP 2450W Platinum Hot Plug
Redundant Power Supply
HP 2650W Platinum Hot Plug
Redundant Power Supply
Power cords (2)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
Output
2450 W 2650 W
Input requirements
Rated input voltage
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current per
line cord
12.2 A at 220/380 VAC
11.2 A at 240/415 VAC
13.1 A at 220/380 VAC
12 A at 240/415 VAC
Maximum input power per
line cord
8064 VA 8646 VA
*Rated 220 VAC to 240 VAC line-to-neutral. The enclosure does not operate from higher line-to-line voltage with the
WYE wall plug configuration. Input AC modules are configured to provide 220 VAC to 240 VAC to the power supplies
in this system.
Hot-plug power supply calculations
For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, see the HP Power Advisor website (http://www.hp.com/go/hppoweradvisor).