power distribution solutions for the ProLiant DL580 G2 server

power distribution solutions for the ProLiant DL580 G2 server
figure 4. single input PDU (shown in 1U mounting configuration)
Several versions of Single Input PDUs are available to meet a variety of electrical
requirements as indicated in Table 4.
table 4. single input PDU types
name, PN voltage /
amperage
AC bus
connector
output connector
type (qty)
16A World Wide,
207590-B21
200-240 / 16 IEC 320 C20
IEC 320 C13 (12)
24A NA/LA/JPN Low,
207590-D71
100-127 / 24 NEMA L5-30P
NEMA 5-15R (12)
24A NA/LA/JPN High,
207590-D72
200-240 / 24 NEMA L6-30P
IEC 320 C13 (12)
32A International,
207590-B31
200-240 / 32 IEC 309
IEC 320 C13 (12)
40A World Wide,
207590-B23
200-240 / 40 Terminal for
hardwiring
IEC 320 C13 (6)
IEC 320 C19 (3)
power/jumper cords
Although PDUs and servers are typically shipped with power cords, a particular
configuration’s physical and/or electrical requirements may require different cords, as
shown in Table 5.
WARNING: Never cut or splice cords to accommodate a configuration.
Personal injury or equipment damage could result in the use of improper
power cords. The correct factory cord should always be used.
7