power distribution solutions for the ProLiant DL580 G2 server
power distribution solutions for the ProLiant DL580 G2 server
low voltage (120
VAC) 3-chassis
power configuration
w/single input PDUs
The following figure shows a configuration of three server units operating off primary
and secondary low voltage busses through two single input PDUs rated at 24 amps
each. With a combined server load of 22.2 amps, approximately 1.8 amps are left for
peripheral devices that in this particular case could be plugged into each PDU’s 9
remaining NEMA 5-15R outlets. The servers are connected to the primary and secondary
PDU modules with C19-C20 jumper cords (PN 178968). These cords are rated at 10
amps each and can easily handle the server’s current drain.
figure 8. low voltage (120 VAC) 3-chassis power configuration w/single Input PDU
table 9. power statistics for low voltage 3-chassis power configuration (w/single input PDUs)
PDU current handling capacity 24 amperes
PDU server load 22.8 amperes
headroom current available for peripheral
devices
3 amperes
power cord used for server-to-PDU jumper NEMA 5-15P to C19 (PN 178968)
120 VAC Primary 120 VAC Secondary
24A Single Input
PDU Module
207590-D71
24A Single Input
PDU Module
207590-D71
DL580 G2 Server
(
120V
,
7.0A
)
DL580 G2 Server
(
120V
,
7.0A
)
DL580 G2 Server
(
120V
,
7.0A
)
NEMA 5-15 Cord
(PN 178968)
12