power distribution solutions for the ProLiant DL580 G2 server
power distribution solutions for the ProLiant DL580 G2 server
low voltage (120
VAC) 3-chassis
power configuration
w/modular PDUs
The following figure shows a configuration of three server units operating off primary
and secondary low voltage busses through two modular PDUs rated at 24 amps each.
With a combined server load of 22.2 amps, approximately 1.8 amps are left for
peripheral devices. The servers are connected directly to the modular PDU’s control core
with C19-C20 jumper cords (PN 295633-B21), which are rated for high voltage but are
also rated at 16 amps so they each can easily handle a 7.4-amp current load. The
extension bars would be necessary for connecting peripherals with NEMA 5-15P power
cords.
figure 7. low voltage (120 VAC) 3-chassis power configuration w/modular PDU
table 8. power statistics for low voltage 3-chassis power configuration (w/modular PDUs)
core current handling capacity 24 amperes
control core server load 22.2 amperes (Power Calculator output using 4 CPUs,
8-GB memory, 72-GB HDD x 4, and 3 PCI cards)
headroom current available for
peripheral devices
1.8 amperes
power cord used for server-to-
control core jumper
C20 to C19 (PN 295633-B21)
120 VAC Primary 120 VAC Secondary
24A Modular PDU
Control Core
252663-D71
24A Modular PDU
Control Core
252663-D71
DL580 G2 Server
(
120V
,
7.4A
)
DL580 G2 Server
(
120V
,
7.4A
)
DL580 G2 Server
(
120V
,
7.4A
)
Ext.
Bar
Ext.
Bar
C20-C19 Cord
(PN 295633-B21)
11