high voltage (230
VAC) 9-chassis
power configuration
Figure 6 shows a configuration where high voltage (230 VAC) is distributed to nine
server chassis in a rack that receives primary and secondary power busses. Each power
bus is handled by a modular PDU that consists of a control core and three extension
bars. Each control core can handle a maximum of 32 amps. In this case, each core
could be called on to provide about 30.6 amps to the servers, leaving a certain amount
of headroom for auxiliary devices, such as KVMs, a TFT display, and rack monitoring
devices.
figure 6. high voltage (230 VAC) 9-chassis power configuration
table 7. power statistics for high voltage 9-chassis power configuration
core current handling capacity 32 amperes
control core load 30.6 amperes (Power Calculator output using 4 CPUs,
8-GB memory, 72-GB HDD x 4, and 3 PCI cards)
headroom current available
for peripheral devices
1.4 amperes
power cord used for server-to-
extension bar jumper
C19 to C14 (PN 291034-B21)
230 VAC Primary 230 VAC Secondary
32A Modular PDU
Control Core
252663-B31
32A Modular PDU
Control Core
252663-B31
Ext.
Bar
DL580 G2 Server
(
230V
,
3.4A
)
Ext.
Bar
DL580 G2 Server
(
230V
,
3.4A
)
DL580 G2 Server
(
230V
,
3.4A
)
DL580 G2 Server
(
230V
,
3.4A
)
Ext.
Bar
Ext.
Bar
DL580 G2 Server
(
230V
,
3.4A
)
DL580 G2 Server
(
230V
,
3.4A
)
DL580 G2 Server
(
230V
,
3.4A
)
Ext.
Bar
C19-to-C14 Cord
Ext.
Bar
DL580 G2 Server
(
230V
,
3.4A
)
DL580 G2 Server
(
230V
,
3.4A
)