table 3: ProLiant DL560 server parameters (continued)
rack rails and hardware weights
Cable arm 0.81 kg (1.8 lb)
Slide (2) 2.07 kg (4.6 lb)
Rail (2) 1.8 kg (4.0 lb)
Total Weight: 4.7 kg (10.4 lb)
relative humidity (non-condensing)
Operating 10 to 90%
Non-operating 5 to 95%
table 4: ProLiant DL560 server power specifications
input voltage
100 115 208 220 230 240
power supply rated output
(W)
550 550 550 550 550 550
nom. input wattage (W) 333 329 325 321 318 314
max. input wattage (W) 503 496 496 490 483 477
nom. input current draw (A) 3.4 2.9 1.6 1.5 1.4 1.3
max. input current draw (A) 5.1 4.4 2.4 2.3 2.1 2.0
nom. input (VA) 340 336 332 328 324 636
max. input (VA) 513 506 506 500 493 487
max. thermal (BTU/Hr) 1715 1693 1691 1670 1648 1628
efficiency (%) 70 72 75 75 75 76
power factor 0.98 0.98 0.98 0.98 0.98 0.98
mom. leakage current (mA) 0.31 0.36 0.65 0.69 0.72 0.75
max. leakage current (mA) 0.63 .72 1.30 1.39 1.44 1.50
nom inrush current (A) @ 20
ms
25 25 25 25 25 25
max inrush current (A) @ 20
ms
50 50 50 50 50 50
Note: These values are derived from a combination of product specifications and
the Power Calculator configured as below in “Nom” and “Max:”
o Nom. = Nominal rating of a unit operating with one or two processors, up to
2 DIMMs, 2 hard drives, one PCI card, and one power supply.
o Max. = Maximum rating of a fully loaded unit: 4 processors, 6 DIMMs, 2 hard
drives, 3 PCI cards, and 2 power supplies.