figure 10: low voltage (120 VAC) 5-chassis redundant power configuration w/modular
PDU
5-chassis redundant power configuration w/modular
PDU
table 12: power statistics for low voltage 5-chassis power configuration (w/modular
PDUs)
table 12: power statistics for low voltage 5-chassis power configuration (w/modular
PDUs)
description value
control unit current handling capacity 24 amperes
control unit server load 22.0 amperes (Power Calculator output
using 4 CPUs, 6-GB memory, 72-GB hard
drives x 2, and 2 PCI cards)
headroom current available for
peripheral services
2.0 amperes
power cord used for server-to-control
unit jumper
C13 to C14 (PN 142256-006) quantity of 1
C13 to C14 (PN 142256-007) quantity of 15
120 VAC Primary 120 VAC Secondary
24A Modular PDU
Control Unit
252663-D71
24A Modular PDU
Control Unit
252663-D71
Ext.
Bar
Ext.
Bar
DL560 Server
(
120V
,
4.4A
)
DL560 Server
(
120V
,
4.4A
)
Ext.
Bar
Ext.
Bar
DL560 Server
(
120V
,
4.4A
)
DL560 Server
(
120V
,
4.4A
)
Ext.
Bar
Ext.
Bar
DL560 Server
(
120V
,
4.4A
)