HP ProLiant DL560 Server High Density Deployment
hp ProLiant DL560 server high-density deployment white paper
27
table 11: power statistics for high voltage 15-chassis power configuration
description value
control unit current handling capacity 32 amperes
control unit load ~15.75 amps under normal operating
conditions with both feeds active
~31.5 amperes under fault condition
where either the primary or secondary
power feed has failed
(Power Calculator output using 4 CPUs,
6-GB memory, 72-GB hard drives x 2, and
2 PCI cards)
headroom current available for
peripheral devices
0.5 amperes
power cord used for server-to-extension
bar jumper
C13 to C14 (PN 142256-006) quantity of 1
C13 to C14 (PN 142256-007) quantity of 15
low voltage
(120 VAC)
5-chassis
redundant power
configuration with
modular PDUs
The following illustration (figure 10) shows a configuration of three server units
operating off primary and secondary low voltage busses through two modular
PDUs rated at 24 amps each. With a combined server load of 22.0 amps, about
2.0 amps are left for peripheral devices. The servers are connected directly to
the extension bars with NEMA 5-15P power cords. Refer to table 12 for power
statistics for the low voltage 5-chassis configuration.