Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks

Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks 15
Compaq Confidential - Need to Know Required
14UH-0701A-WWEN
Power Cords
The power cord included with the North American model of the ProLiant DL380
Generation 2 server can be used for low-voltage applications. Use a 1.8-m (6-ft) to 2.4-m (8-ft)
long power cord with the standard rack rails and cable management arm.
For information on obtaining high-voltage power cords, visit the Compaq website:
www.compaq.com
Table 8 lists PDU configurations for 42U racks and Table 9 lists PDU configurations for 36U
racks. The configurations in these tables refer to racks that are fully populated with servers. Racks
fully populated with servers use either an off-rack console management system or a remote
console management system. For an example configuration of a rack using an in-rack console
management system, see Figure 3.
Table 8. PDU Configurations for 42U Racks
Vertical Mount Bracket Kits
Part Number
Input Voltage/
Current Rating
166097-B21
with Y-cables
191265-B21
Maximum
Servers
PDUs per
Rack
Populated Rack
Weight (lb)
BTUs
207590-B21 High/16 A 2 5 4 1,813 29,400
207590-D71 Low/24 A 3 4 1,813 29,400
207590-B31 High/32 A 2 10 3 1,800 29,400
207590-D72 High/30 A 2 7 3 1,800 29,400
191186-001 High/24 A 2 7 3 1,800 29,400
191186-B31 High/30 A 2 9 3 1,800 29,400
197616-B22 High/32 A 2 12 2 1,787 29,400
295363-001 Low/24 A 1 3 4 1,813 29,400
295363-002 High/16 A 2 5 4 1,813 29,400
295363-003 High/24 A 2 7 3 1,800 29,400
295363-291 Low 24 A 1 3 4 1,813 29,400
295363-B21 High/16 A 2 5 4 1,813 29,400
295363-B32 High/16 A 2 5 4 1,813 29,400