Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks
Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks 12
Compaq Confidential - Need to Know Required
14UH-0701A-WWEN
Table 6. Compaq PDUs (continued)
Part Number
Availability
Input
Voltage
Current
Rating
Maximum
Servers per
PDU
1
Input
Connectors
and Cord
Output
Connectors
Output
Breakers
Dimensions
Weight
191186-001
2
North America High 24 A 7 NEMA L6-30P
2 × 12-ft cord
12 × IEC 320-C13 4 × 10
A
4.37 × 30.48 × 43.18 cm
1.72 × 12.0 × 17.00 in
9.1 kg
20 lb
191186-B31
2
International High 30 A 9 IEC 309-32A
12-ft cord
12 × IEC 320-C13 4 × 10
A
4.37 × 30.48 × 43.18 cm
1.72 × 12.0 × 17.00 in
9.1 kg
20 lb
197616-B22
3
Worldwide High 40 A 12 Field wiring
12 × IEC 320-C13
1 × DB9 Serial
1 × RJ-45
4 × 10
A
4.32 × 43.18 × 50.04 cm
1.70 × 17.00 × 19.70 in
6.4 kg
14 lb
295363-001
4,5
North America Low 24 A 3 NEMA L5-30P
12-ft cord
12 × NEMA 5-
15R
2 × 15
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
5.4 kg
12 lb
295363-002
4,5
North America High 16 A 5 NEMA L6-20P
12-ft cord
12 × IEC 320-C13 2 × 10
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
3.6 kg
8 lb
295363-003
4,5
North America High 24 A 3 NEMA L6-30P
12-ft cord
12 × IEC 320-C13 4 × 10
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
5.4 kg
12 lb
295363-291
4,5
Japan Low 24 A 3 NEMA L6-30P
12-ft cord
12 × NEMA 5-
15R
2 × 15
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
5.4 kg
12 lb
295363-B21
4,5
Worldwide High 16 A 5 IEC 320 C-20
12 × IEC 320-C13 2 × 10
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
5.4 kg
12 lb
295363-B32
4,5
International High 16 A 5 NEMA 309-16A
12 × IEC 320-C13 2 × 10
A
5.03 × 25.15 × 48.97 cm
1.98 × 9.9 × 19.28 in
5.4 kg
12 lb
Note 1: These numbers are determined using a single power source (non-redundant).
Note 2: This PDU supports power from two different sources. If one power source fails, the PDU uses the alternate source.
Note 3: This PDU must be hard-wired to the power source by a certified electrician.
Note 4: This PDU requires Compaq Vertical Mount Bracket kit (PN# 191265-B21 or 166097-B21 with high-voltage Y-cables) to vertically mount
in rack side panel.
Note 5: This PDU is no longer being shipped by Compaq.
In Compaq 7000- and 9000-series racks, the 295363-xxx PDU series must be installed vertically
in the rack side panels to prevent interference with the server rack rails. Compaq Vertical-Mount
PDU Bracket kits enable PDUs to be mounted vertically in the side compartments of 7000- and
9000-series racks. Compaq offers two Vertical-Mount PDU Bracket kits:
• Compaq Vertical-Mount PDU Bracket (P/N 191265-B21): This kit includes eight brackets
that support four PDUs. This kit works best with low-voltage applications that use the power
cord included with the server.
• Compaq Vertical-Mount PDU Bracket with High-Voltage Cables (P/N 166097-B21): This kit
includes 11 Y-cables and 4 brackets that support 2 PDUs. This kit works best with high-
voltage, high-current PDUs. Using the Y-cables enables each power outlet on the PDU to
supply power for 2 servers.