4.3.5.11. High Voltage 2-PDU Cabling Diagram with Y-Cables (22U Rack)
Figure 4-15. 22U rack cabling diagram for 2 PDUs with y-cables
Notes
• See Section 4.3.3 for power cord information and power cord routing choices.
• The high voltage PDUs shown in this figure are 24A rated.
• One Vertical-Mount PDU Bracket Kit with High Voltage Cables is required for this installation.
• For PDU-1, there are 8 Y-cables connected to the PDU to support 16 servers in the above figure.
Each of the 8 Y-cables is connected to two servers.
• For PDU-2, there are 6 power outlets still open (marked with **). 16.8A of current capacity has been
allocated for the servers. The total current draw from the remaining outlets by other off-rack devices
must not exceed 7.2A for the 24A PDU.
• No power cords should be connected to all the unused outlets marked with Ø.
PDU-1 PDU-2
1 Line (200-240V
)
1 Line (200-240V)
**
11 Y Power Cords
10A
10A
10A
10A
PDU-2
10A
10A
10A
10A