Ultra-Dense Server Deployment in Racks
Compaq Ultra-Dense Server Deployment in Compaq Racks 71
128H-0400A-WWEN
4.3.5.10. Low Voltage 4-PDU Cabling Diagram with Single Cables (36U Rack)
Figure 4-14. 36U rack cabling diagram for 4 PDUs with single cables
Notes
• See Section 4.3.3 for power cord information and power cord routing choices.
• The low voltage PDUs shown in this figure are 24A rated.
• One Vertical-Mount PDU Bracket Kit is required. The power cords that came with the
ProLiant DL360 servers can be used in this configuration.
• All the PDUs current capacity has been allocated for the servers and the other devices in the rack.
• No power cords should be connected to all the unused outlets marked with Ø.
PDU-2
PDU-1
PDU-3
PDU-4
2 lines (100-120V)
2 lines (100-120V)
36 Power Cords
15 A
15 A
15 A
15 A
15 A
15 A
15 A
15 A
22 Server 22
21 Server 21
20 Server 20
19 Server 19
17 Server 17
18 Server 18
16 Server 16
15 Server 15
14 Server 14
13 Server 13
12 Server 12
11 Server 11
10 Server 10
35 Server 35
36 Server 36
34 Server 34
33 Server 33
32 Server 32
30 Server 30
31 Server 31
29 Server 29
28 Server 28
27 Server 27
26 Server 26
25 Server 25
24 Server 24
23 Server 23
8 Server 8
9 Server 9
7 Server 7
6 Server 6
5 Server 5
4 Server 4
3 Server 3
2 Server 2
1 Server 1