Ultra-Dense Server Deployment in Racks
Compaq Ultra-Dense Server Deployment in Compaq Racks 60
128H-0400A-WWEN
4.3.2.4. Mounting 4 PDUs
A 36U or a 42U rack can accept up to four Compaq PDUs – one in each half side-panel compartment.
There are no special location considerations when mounting four PDUs.
4.3.3. PDU Cord Set Choices
This section explains the Compaq high voltage and low voltage power cord choices.
4.3.3.1. High Voltage Power Cords
The Power Y-Cables shipped with the Vertical-Mount PDU Bracket Kit with High Voltage Cables are 10
ft long cable, where the “single” side is 6 ft long and the “double” side is 4 ft long as shown in Figure 4-3.
These Y-cables are optimized to work with both fixed-rails and sliding-rails installation, and they are
designed to work with Compaq High Voltage PDUs.
Figure 4-3. Power Y-cable and the connector types in P/N 166097-B21.
Table 4-2. High Voltage power cord choices.
Description Compaq P/N Note
Vertical-Mount PDU Bracket with High
Voltage Cables Kit
166097-B21 There are 4 PDU brackets and 11 Y-cables in this kit.
Each cable is 10 ft long and has 6 ft section on the
single-side and 4 ft sections on the dual-side.
10A 7ft Y-Cable Available
3Q00
There are 6 Y-cables in this package. Each cable is 7
ft long and has 4 ft section on the single-side and 3 ft
sections on the dual-side.
10A IEC-to-IEC jumper cables kit 6 ft
8 ft
12 ft
142257-001
142257-002
142257-003
If a longer cable is needed for the high voltage Y-
power cords, then the IEC-to-IEC jumper cables can
be used to extend their length.
4 ft sections
6 ft sectio
n
IEC 320-C13
(each connects to a
ProLian
t
DL360
)
IEC 320-C14
(connects to a PDU outlet)
Y-junction